When a transient, or permanent fault occurs, which exceeds the set fault current in Smart FID, special automatic trigger algorithm Permanent Fault and as the upstream Recloser trips, the circuit line current falls to Zero. The logic circuit recognizes Dead Line that follows fault current and commands 1 or all 3 phases to open simultaneously.
The message is sent via SMS or to SCADA / Cloud. After SFID opens, the upstream Recloser, or Circuit Breaker shall close successfully on the next trial.

| Technical Data | ||
|---|---|---|
| Rated Voltage(BIL) | KV | 15 KV (110) |
| KV | 27 KV (125 / 150) | |
| KV | 38 KV (150 / 170) | |
| Rated Current | A | 100 , 200 |
| Rated Frequency | Hz | 50 / 60 |
| Minimum Line Current (Self Charging) | A | 1 (2) |
| FID Open by Fault Trigger | Sec | Settable Time 1~ 180 sec (or, Counts 1 ~4 Option) |
| Reset Time | Sec | 180 |
| Inrush Detection Time | Ms | 0 ~ 100 |
| Short time current withstand, 15 cycle | kA | 12.5 |
| Current measurement accuracy: | ±10 % (Option : 5 %) | |
| Temperature range | -40°C to +80°C | |
| Surge current withstand | 65KA, per ANSI C37.63 | |
| Electromagnetic interference | ANSI C37.63 | |
| Radio frequency interference | ANSI C37.90.2 | |
| Program method | Wireless Programmable | |
| SCADA System Protocol | DNP3.0, or IEC 101, IEC 104 | |
| Mobile phone Control and Monitoring | Via SMS Message | |
| GPS system (Option) | Google Map operation | |
| Compatible use with Existing COS body | Yes | |